Short answer
Chimney requirements come from building codes, such as the International Residential Code (IRC) sections on fireplaces and chimneys, and from NFPA 211. Factory-built units follow the manufacturer’s listing. Local adoption and amendments vary, so confirm the rules with your local building department before you build, buy or change anything.
Chimney height: the 3-2-10 rule
A masonry chimney must extend at least 3 feet above the point where it passes through the roof. It must also be at least 2 feet higher than any roof, building or structure within 10 feet horizontally. Both conditions must be met. For the full method, see what the 3 to 10 rule for chimneys is.
Clearance to combustibles
- Masonry chimney: combustible material should be kept at least 2 inches from an interior chimney, and at least 1 inch from a chimney that is wholly outside the building.
- Airspace: the gap around the chimney should not be filled with insulation or other material, except for noncombustible fireblocking at floors and ceilings.
- Factory-built chimney: the clearances are set by the manufacturer’s listing, and they differ from masonry numbers. Use the maker’s instructions.
Hearth and firebox
- Hearth extension: the code generally calls for at least 16 inches in front of the opening and 8 inches to each side. For an opening of 6 square feet or more, the extension is 20 inches in front and 12 inches to each side.
- Hearth thickness: the extension is typically at least 2 inches thick and noncombustible. The hearth under the firebox is typically at least 4 inches thick.
- Mantels and trim: combustible trim should not be within 6 inches of the opening. Trim between 6 and 12 inches away can project only a small amount, as the code sets out.
- Firebox depth: at least 20 inches for a standard masonry firebox. A Rumford design can be shallower, around 12 inches.
- Firebox walls: 10 inches of solid masonry, or 8 inches including a 2-inch firebrick lining.
Chimney walls, liner and flue size
- Chimney walls are typically at least 4 inches of solid masonry, with a flue liner.
- Flue area is usually sized as a fraction of the fireplace opening, roughly one-tenth to one-twelfth depending on the flue shape and chimney height. An installer or inspector should confirm the size.
- A flue that is too large can draft poorly and build up creosote, so do not oversize it.
Caps, spark arrestors and crickets
- A spark arrestor mesh at the top should have openings between 3/8 inch and 1/2 inch.
- A cricket, a small peaked structure behind the chimney, is generally required where a chimney is more than 30 inches wide on a sloped roof.
Permits and inspections
Most areas require a permit for a new or modified fireplace or chimney, followed by inspections. Insurers often ask for proof of permits and inspections, so keep the paperwork. The inspection will check clearances, height and liner details.
Common problems
- An old, unlined masonry chimney is not automatically safe to use.
- A cracked or missing liner can let heat and gases reach the structure, and it creates a fire and carbon monoxide hazard. If you are in doubt about a chimney’s condition, get a Level 2 inspection before using it. For how a chimney can become a fire hazard, see chimney fires: early warning signs and what to do.
- Insulation or storage packed into the airspace around a chimney is a code problem and a fire risk.
- Nearby trees or taller buildings can cause draft problems even when the chimney meets the height rule.
For wood stove flues and connectors, see does a wood burning stove need a flue.